Electric shock, Fire

0512/06

image
Case number
0512/06
Category
Electrical appliances and equipment
Audience
Consumer
Notifying country
🇩🇪 Germany
Country of origin
Unknown
Published
2006-08-18

⚠️ Risk

This product poses a risk of electric shock and fire due to insufficient cross section area. The extension cord does not comply with the Low Voltage Standard because it has the cross-section area of 0.5 – 0.75 mm² while the extension cord having a length of more than 2.00 m must have the cross-section area of at least 1.5 mm². The protective conductor is therefore no longer sufficiently functional. There is also a danger that the cord will become overloaded, which may cause fire. The electric cord does not contain any information/warning.

Measures

Type of economic operator taking notified measure(s): OtherCategory of measure(s): Voluntary recall and destruction of the product by the importer.Date of entry into force: Unknown

Extension cord “Laudmann”Type/number of model: 1. LM-690, 2. LM-691 and 3. LM-692.Description: 1. LAUDMANN extension cord, 3m long, LM-690;2. LAUDMANN extension cord, 5m long, LM-691;3. LAUDMANN extension cord, 10m long, LM-692.